Product Center

Product Classification
ZM-DDL Low voltage Dynamic Filtration Reactive Compensation Device

Print current page

Product Description

  • brief introduction
  • technical parameter
  • Product size

Application

It is widely use in the distribution system of power industry, metallurgy, railway, military, petroleum, machinery, chemical industry, light industry, building material, mineral, shipbuilding and etc, where both dynamic reactive compensation and harmonic filtration are required


General

While technology developing, plenty of electronic and power equipment are put into use, so the conflict between dynamic reactive compensation (fast tracking reactive compensation) and harmonic treatment is more and more obvious, ZM-DDL series intelligent dynamic reactive compensation equipment adopted the advanced power and electronic technology, information technology, intelligent control technology, to solve the interference of harmonic waves to the switching of shunt capacitors, also eliminate the harmonics according to the actual requirement, purify the power network, as a new generation of smart type dynamic reactive compensation and harmonic filtration complete set equipment.


Function

Effectively support system voltage, ensure the system run in normal state and keep high power factor, avoid penalty, also improve the using rate of equipment

Effectively restrict harmonics

Lessen loss and save energy


Model and implication


Main technical data

Rated voltage: three grades 400V、660V、1100V respectively (other value can be designed)

Dynamic response time: ≤20ms

Rated measured current: 5A

Harmonic measurement scope: 1 ~ 25 times

Accuracy: voltage, current: 0.5class, power: 1.5class

Reactive compensation of basic wave: power factor up to 0.9~0.95

Harmonic filtration rate: non-standard filtration type, complied with the requirement of GB/T14549-93Y standard

Standard tuning type: filtration rate of 5th power of harmonics >50%

Stabilized voltage scope: complied with the requirement of GB 12326-90 standard, △U≤+2%

Whole power dissipation: ≤1% of rated capacity of device

Structure figure: panel structure, free standing.Protection grade: IP41, outdoor use type: IP43 (others can be designed)

Installation: execute in compliance with the requirement for general power panel and switchgears.


Technical Features

Switching at zero current

Large-scaled transistor current through-zero switching technology, can switch on/off capacitors at zero current, no surge, no impulse,

Fast dynamic response

Fast tracking the change of load in the system, correspond dynamically to switching on/off at real time, response time <20mS

Intellectualized

Assembled with smart detection terminal, combine the dynamic reactive compensation device with automatic system of the distribution network, realize the control of instantaneous switching, the local monitor of the related electricity quality, parameters, and remote operations as remote measurement, remote communication, remote control, meanwhile over-current, over-voltage, under-voltage, three-phase imbalance, temperature protections provided.


Principle Description

Standard tuning type:

It is mainly used in the system where has a little harmonics and the load change very quickly. Generally, the simple reactive compensation device can't be used for such system, because it has three problems: firstly shunt capacitors will amplify the harmonics, capacitor bank and system will form parallel resonance, make harmonic current to be enlarged, further the distortion of voltage and current will be more severe; Secondly the direct influence on shunt capacitors, harmonic current superimposed on basic wave, effective current rise up and lead to high temperature rise, this will shorten the service life of capacitors; thirdly it is difficult to track the quickly changed load, easy to over compensation or under compensation, then system voltage fluctuation happen. Regarding these problems, for the system with harmonic contents less than 30%, reactive compensation device shall be directly series connected with tuning reactor, make the resonance freq of this loop less than lowest power of harmonic wave, and make the current as capacitive value at power frequency namely improving power factor, and make current as inductive value at resonance freq, namely preventing resonance and amplification. Our tuning type standard ZM-DDL dynamic reactive compensation device can absorb more than 40% of 5th, 7th powers of harmonic waves


Custom-Made
主站蜘蛛池模板: 一本色道久久综av蜜桃臀 | 美女牲交视频一级毛片动态图 | 亚洲第一无码xxxxxx | 国产高潮流白浆喷水在线观看 | 在线亚洲一区二区 | free欧美日韩免费在线观看 | 日韩精品一区二区三区视频 | 97涩涩网| 2020国产在线拍揄自揄视频 | 免费视频精品一区二区 | 免费高清av | 中文字幕乱码亚洲无线三区 | 亚洲视频天天射 | 黄色录像一级片子 | 亚洲区小说区综合图片 | 欧美日韩小视频 | 久久久久蜜桃精品成人片公司 | 五级黄毛片 | 大学生a级毛片免费视频 | 国产在线播精品第三 | 欧美一区二区三区中文字幕 | 精品国产亚洲一区二区在线3d | 亚洲午夜久久久久久久久 | 超级无码视频在线观看 | 亚洲操比 | 黄页在线免费观看 | 国产一级片内射免费视频播放 | 欧美黄一区 | 国产18禁黄网站免费观看 | 国产精品久久嫩一区二区 免费 | 刘亦菲人久久精品二区三区 | 免费色视频在线 | 国产亚洲欧洲997久久综合 | 久久久成人999亚洲区美女 | 精品国产91久久久久久久妲己 | 天天摸天天透天天添 | 国产露脸150部国语对白 | 91爱爱影院 | 成年人网站在线观看视频 | 福利视频在线免费观看 | 久久妇女高潮几次MBA |