ZMFK series intelligent compound switch

Print current page

Product Description

  • brief introduction
  • technical parameter
  • Product size

Code and Implication

Three-phase integrated compensation type: Theconnection mode of capacitor is delta connection.

Single-phase separate compensation type: Theconnection mode of capacitor is star connection.


? ? ?

Functions and features

Switching while pass through zero:

Depending on intelligent chipset and digital circuit and magnetic holding relay, ZMFK combined switch perform switching on when voltage passing through, and switching off while current passing through zero, make the switch opened or closed at zero value, not produce over-voltage. Also it has no surging current, low power loss, high service life, low fault and etc, they are widely used in the field of low voltage reactive power compensation.


Protection function:

Use microprocessor to monitor and control switching relay and the operation status of input source and load, provide complete protection functions

1. Protection against system over-voltage, under-voltage: when these faults occur, it will switch off automatically, and the indicator is ON for warning.

2.Protection of phase failure: if any phase is lost, it will switch off automatically, and the indicator is ON for warning.

3.Protection of power off: when the power is ON, but out of power failure suddenly, it will switch off automatically.

4. Protection of no-load: if the system has no load, closing operation will be not performed, and the indicator will flash for warning.

5.Indicate the switch status of each phase, indicators: continuous ON means normal, flashing means: over-voltage, under-voltage or phase failure, A/B/C phase status indicator ON, continuous lighting, means the switch closed, the indicator of some phase flashing, means this phase has fault, or the capacitor of this phase is delayed under discharging.

Self-diagnosed fault: If any phase has fault, it will reject action, indicator flash for warning.

Combined switch does not need to connect with N line.
Low power loss:

Magnetic holding relay will consume power only at the time of switching, otherwise it will not need power.
Operation safety:

All input signal for control are safely isolated from inner circuits, meanwhile the advanced intelligent control technology is adopted, in comparison with similar products, our type has smaller surge, and more reliable. Input signal is isolated from combined switch through photoelectric mode, high EMC protected facility, anti-interference, safe operation.


Main technical indicators

Ambient temperature: -20°C~+55°C;

Relative humidity: 40°C when, 20%~90%;

Rated voltage: 380V/220V, AC 50Hz;

Permissible deviation: The synchronous change of three phase voltage is not more than ±20%;

Degree of distortion is less than 5%;

Rated frequency: 50HZ;

Rated current: 45/55A;

Service life: 500,000times;

Number of phase: Three phases (△-connection) and single phase(Y-connection)

Control capacity: ≤40Kvar at three-phase integratedcompensation

Single-phase separate compensation:≤13.3Kvar;

Power consumption: ≤1.5VA;

Contact voltage drop: ≤100mV;

Contact withstand voltage: ≥1600V;

Response time: ≤100ms;Interval of every making and breaking:≥5s;

Interval of continuous two makings: ≥35s;

Startup voltage: DC12V±20%;

Input impendence: ≥6.8K;

Conduction impendence: ≤0.003Ω;

Inrush current: <1.5 In


specification

Installation and wiring methods

This combined switch is used in 380V distribution network, to control the switching on/off of reactive capacitors. Input side need three-phase lines only, N line not required, the cable shall use proper multi-core copper conductor in consideration of otal three-phase capacity, if total capacity less than 30KVAR, 10sqmm multi-core cable can be used, for 30KVAR and above, please use 16sqmm or larger one, cable connector/lugs shall be pressed tightly by screw/bolt, otherwise overheating will lead to damaging the product.

Outline size: L 160 x W 96 x D 95 mm

L 212 x W 106 x D 85 mm

Fixing hole distance: L 142 x W 80mm/L 199 x W 88mm



wiring diagram



主站蜘蛛池模板: 国产精品网站在线看 | 在线观看免费高清播放 | 亚洲二三区 | 国产一区二区三区免费播放 | 在线国产福利在线观看 | 国产1区2区3区中文字幕 | 姑娘第7集在线观看 | 国产一级女医生av毛片 | 亚洲AV秘无码一区二区三区一 | 国产人成视频在线视频 | 国产一区在线播放 | 一个人免费观看www高清中文 | 欧洲另类交 | 激情四射五月天婷婷 | 午夜男人在线观看 | 中文字幕国语版毛片免费 | 欧美亚洲色欲色一欲WWW | 一级全毛片 | av天堂中文字幕在线播放 | 日本超碰在线 | 久久久久无 | zzzwww在线观看免 | 嗯好大好爽高潮了av大片 | 国产精品乱码人人做人人爱 | 日干夜操| 国产亚洲精品拍拍拍拍拍 | 在线观看一区三区 | 国产精品成人久久 | 亚洲好穴| 免费在线a| 免费看色网站 | 精品h视频 | 亚洲第一无码av无码专区 | 91看片在线观看 | 91超碰青青频精品国产 | 国产乱码精品一区二区三区中文 | 精品欧美一区二区三区免费观看 | 欧美激情一区二区三区四区 | 国产精品成人a区在线观看 久久一区二区av | 国产乱子伦农村叉叉叉 | 国产一级一级片 |